Champion 8.5KW with NEMA 3 50amp switch
Champion 8.5KW with NEMA 3 50amp switch

Call for Price
50 amp Champion Automatic Transfer Switch, NEMA 3, Outdoor Use (Model 100950)
Features
- 8.5kW continuous electrical power
- 439cc Champion OHV engine, electric start and low oil shut down
- Automatic 50 amp, 10 circuit indoor transfer switch
- Champion Auto Control Module (ACM)
- All weather composite mounting pad
- All weather steel enclosure
- Natural gas (NG) or Propane (LPG) operation
- 5 year limited warranty
- 100 percent reliable
- 24 volt starting system is the most powerful in the industry. Designed to assure starting at temperatures as low as -22 degrees F
- Quietest in class. Comparable to normal conversation.
50 amp Champion Automatic Transfer Switch, NEMA 3, Outdoor Use (Model 100950)
Specifications:
kW (LPG) | 8.5 |
kW (NG) | 7.5 |
LPG Rated Load (A) | 70.8/35.4 |
NG Rated Load (A) | 62.5/31.25 |
Rated Voltage | 120/240 |
Main Line CB (A) | 36 |
Phase | 1 |
Rotor Poles | 2 |
Frequency | 60 |
Insulation Class | H |
THD (%) | <5% |
Power Factor | 1 |
Weight (lbs) | 365.1 lbs |
Dimensions | L 49.1" X W28" X H28.3" |
Enclosure Material | Steel |
Enclosure Base Material | Composite |
Normal Operation Noise Level, Installed | 59.5 dBA at 23 ft. (7 m); In front of generator |
Operating Range °F(°C) | -22°(-30°) to 104°(40°) |
Engine Specifications
Type: Champion | OHV |
Displacement (cc) | 439 |
Engine Speed (rpm) | 3600 |
Block Material | Alum with Cast Iron Sleeve |
Carburetor Type | 1-barrel |
Governor Type | Mechanical |
Ignition System | Solid State Magneto |
Starter | 24V |
Oil Capacity (qt/L) | 1.2/1.1 |
Oil Cooler | No |
EPA Certified | Yes |
Fuel Consumption
NG Fuel Consumption @ 50% load (m3/hr) | 2.76 |
NG Fuel Consumption @ Full load (m3/hr) | 3.96 |
LPG Fuel Consumption @ 50% load (l/hr) | 4.00 |
LPG Fuel Consumption @ Full load (l/hr) | 5.67 |
Fuel Supply Inlet (NPT) | 3/4 |
* Fuel pressure required for NG | 6" w.c. |
* Fuel pressure required for LPG | 11" w.c. |
Control Features
Engine Mode: ATS | Automatically starts on utility failure |
Engine Mode: Manual | Starts unit and runs until turned off |
Engine Mode: Off | Stops unit / controller and charger active |
Transfer Switch Mode: Auto | Automatically transfers power on utility failure |
Transfer Switch Mode: Off | Does not transfer power on utility failure |
Transfer Switch Mode: Test | Tests all components without starting generator |
Generator State Indicator | Standard |
Programable Start Delay | Standard |
Weekly Exercise | Automatically starts, runs for 15 min |
Engine Starting | Crank sequence up to five attempts |
Starter Lockout | Cannot restart for 5 sec after engine stopped |
Low Battery Indicator | Standard |
Battery Charger Fault Indicator | Standard |
Engine Warm Up | 20 sec |
Engine Cool Down | 1 min |
Low Oil Shutdown | Standard |
Overspeed Shutdown | Standard |
High Engine Temp Shutdown | Standard |
Overcrank Protection | Standard |
Under Speed Protection | Standard |
Over Speed Protection | Standard |
Continuous Battery Charging | Standard |
Hour Meter | Standard |
Exterior Failed Start Indicator | Standard |
Utility Voltage Monitor | Standard |
Safety Fuse | Standard |
Failure to Transfer Protection | Standard |
Reverse Polarity Protection | Standard |